Parameter Specification
Product Model DG4V-3-8B-LW-V-M-U-H-L-761
Product Line Eaton DG4V Proportional Valves
Valve Type 4-way, 3-position proportional directional valve
Service Rating (Size) 03 (Nominal flow ~10 US gpm / 38 Lpm)
Maximum Operating Pressure Typically 350 bar (5000 psi)
Solenoid Type Wet Pinion Solenoid (LW)
Coil Voltage 12 V DC
Spool Feedback LVDT (H) for precise closed-loop control
Manual Override Yes (U)
Electrical Connector Specific type (M)
Seal Material Buna-N (L)
Technical Parameters
Category Specification
Model DRAQ127-220-R
Product Type HMI + PLC All-in-One Panel PC
Display
Screen Size 7 inches (diagonal)
Resolution 800 x 480 pixels (WVGA)
Touchscreen Projected Capacitive (PCAP) / Multi-touch
Processor (CPU) Intel Atom E3845, Quad-core, 1.6 GHz
Memory (RAM) 4 GB DDR3L (soldered)
Storage 32 GB eMMC (onboard)
Operating System Windows 10 IoT Enterprise (pre-installed)
Power Supply 220V AC (typically 100-240V AC wide range)
Communication Ports
Ethernet 2 x Gigabit Ethernet (10/100/1000 Mbps)
USB 4 x USB 2.0 ports
Serial (COM) 2 x RS-232/422/485 (software-configurable)
Expansion 1 x Mini PCIe slot (for additional modules like Wi-Fi/4G)
PLC Functionality Integrated runtime for Eaton's PLC software (e.g., XSoft-CODESYS)
Protection Rating IP65 (front panel) - Dust-tight and protected against water jets
Operating Temperature Typically -20°C to +60°C (confirm specific rating in official datasheet)
Technical Parameters
Category Specification
Model T5-4-8903/I5-SI
Product Type 4-Quadrant Digital DC Drive
Input Power
Supply Voltage Typically 400V AC, 3-Phase (Confirm based on "4-" prefix and region)
Frequency 50/60 Hz
Output Power
Armature Output 15 HP / 11 kW (This is a common rating for this frame size, e.g., 8903)
DC Armature Voltage Typically 0-500 V DC
Field Supply Typically 0-300 V DC (for motor field excitation)
Control
Control Type Digital, 4-Quadrant (Regenerative)
Speed Regulation Typically < 1% of base speed (with tachometer)
Typically 2-5% of base speed (armature voltage feedback, IR comp)
Interface Digital Keypad with Display
Communication Optional communication modules (e.g., DeviceNet, Profibus, Modbus)
Features
Diagnostics Comprehensive fault logging and status monitoring
Protections Overcurrent, Overvoltage, Undervoltage, Overload, Heatsink Overtemperature, Field Loss, etc.
Programming Via keypad or PC software (e.g., Eaton's Drive Setup Software)
Enclosure Typically supplied as a chassis unit for panel mounting (IP00). Requires an external enclosure for protection.
Technical Parameters
Category Specification
Model MTL5575
Product Type Safety Relay Module / Safety Loop Monitor
Typical Safety Standard IEC 61508, IEC 61511 (SIL 2 capable)
Input Channels Typically one or two Dual-channel inputs (for monitoring E-Stop circuits etc.)
Input Type Dry contacts (volt-free contacts) from safety devices.
Outputs 3 C/O (Changeover) relays - 2 "Auxiliary" and 1 "Safety".
Contact Rating Typically 8 A, 250 V AC / 5 A, 30 V DC (resistive)
Supply Voltage 24 V DC (nominal), with a wide operating range (e.g., 19-32 V DC).
Key Features
Fault Detection Yes. Automatically detects cross faults, earth faults, and loss of supply.
Reset Modes Manual, Automatic, or Monitored reset (selectable).
Status Indication LED indicators for Power, Inputs, and Faults.
Safety Integrity Level Suitable for SIL 2 applications (as per specific safety manual).
Operating Temperature -40°C to +70°C (standard for industrial MTL products).
Mounting Standard 35 mm DIN rail.
Safety Function Upon a valid input signal or detected fault, it de-energizes the safety relay, breaking the circuit to the controlled device.
Technical Parameters
Category Specification
Model MTL5044
Product Type Foundation Fieldbus H1 Power Conditioner & Repeater
Compliance Designed to meet Foundation Fieldbus H1 standards.
Network Topology Supports trunk-and-spur topology.
Primary Function Signal Conditioning, Repeater, and Power Supply for the fieldbus segment.
Signal Repeater Yes. Regenerates the digital signal, extending the network range.
Number of Ports Typically 4 isolated fieldbus ports, allowing it to create a network hub.
Power Supply Requires an external 24V DC power source (input). Provides conditioned power to the fieldbus.
Key Features
Segment Protection Includes short-circuit protection for each output port.
Diagnostics LED status indicators for power, network activity, and faults.
Isolation Provides galvanic isolation between ports and from the power supply.
Typical Use Case Used in conjunction with intrinsic safety barriers (e.g., MTL5043) to build a complete FISCO / Entity approved Fieldbus system in hazardous areas.
Mounting Standard DIN rail mount.
Operating Temperature -40°C to +70°C (standard for industrial MTL products).
Technical Parameters
Category Specification
Model MTL5841
Product Type Configurable Safety Relay / Safety Controller
Safety Standards IEC 61508, IEC 62061, ISO 13849, NFPA 79
Safety Level SIL 3 (IEC 61508) / PL e (ISO 13849)
Input Channels Typically 2 or 4 configurable input channels for safety devices (e.g., dual-channel).
Input Type Monitors dry contacts (volt-free) or solid-state signals from safety devices.
Outputs 2 or 3 safety relay outputs (force-guided contacts).
Contact Rating (Output) Typically 6 A, 250 V AC / 5 A, 30 V DC
Supply Voltage 24V DC (with a wide range, e.g., 19.2 - 30V DC)
Configuration Via DIP switches or PC software (e.g., MTL SRS-2 Software), depending on the variant.
Key Features
Function Library Pre-configured for functions like E-Stop, Safety Gate, Two-Hand Control, etc.
Fault Detection Yes. Automatically detects cross faults, short circuits, and loss of supply.
Reset Modes Manual, Automatic, or Monitored reset (configurable).
Status Indication Comprehensive LED indicators for Power, Input Status, Output Status, and Faults.
Diagnostics Extensive diagnostic capabilities for easy troubleshooting.
Mounting 35 mm DIN rail.
Operating Temperature -25°C to +55°C / -40°C to +70°C (depending on variant)
Technical Parameters Category Specification
Model MTL5081
Product Type 2-Wire Loop-Powered Isolator
Input Signal 4-20 mA (standard process current signal)
Output Signal 4-20 mA (isolated replica of the input)
Power Supply Loop-Powered. Operates from the signal loop itself, typically requiring a minimum loop voltage (e.g., 12-30 V DC) at the input.
Isolation Galvanic Isolation between input and output circuits. A typical isolation rating is 1500 V AC.
Key Features
Ground Loop Elimination Yes. Prevents stray ground currents from affecting the signal.
Noise Suppression Provides common-mode noise rejection.
Intrinsic Safety When used with an associated intrinsic safety barrier, it can be part of a loop for hazardous areas.
Accuracy Typically ±0.1% to ±0.2% of span.
Load Capacity The maximum output load (e.g., 500-750 Ω) is limited by the available loop supply voltage.
Mounting Standard 35 mm DIN rail.
Operating Temperature -20°C to +60°C
Technical Parameters
Category Specification
Model SL7/4-FW
Product Type Three-Phase Multi-Function Power Meter
Inputs
Voltage 3-Phase + Neutral. Typical nominal voltages: 230/400V AC, 277/480V AC, etc.
Current Via external Current Transformers (CTs). Standard secondary inputs: 1A or 5A.
Measured Parameters
Basic Volts (V), Amps (I), Frequency (Hz)
Power Active, Reactive, Apparent Power (kW, kvar, kVA)
Energy Import/Export Active and Reactive Energy (kWh, kvarh)
Power Quality Power Factor (PF), THD, Demand
Communication
Protocol** Modbus TCP/IP (via integrated Ethernet port)
Port RJ45 Ethernet
Display Built-in LCD or LED display for local readout of parameters.
Key Features
Data Logging Typically includes historical data and demand profiling.
Alarms Configurable setpoints for alarm relays.
Auxiliary Supply Requires a separate auxiliary power supply (e.g., 80-270V AC/DC or 24V DC).
Mounting Panel-mounted, designed for a standard cutout.
Technical Parameters
Category Specification
Model MTL5511
Product Type Zener Diode Safety Barrier (for Digital Inputs)
Certification ATEX, IECEx, etc. (for Intrinsic Safety)
Application Protection of digital (discrete) input circuits.
Number of Channels Single channel.
Key Safety Parameters
Voltage (Um) 250 V AC/DC (Maximum voltage allowed in the safe area)
Open-Circuit Voltage (Uoc) 28 V (Maximum voltage the barrier can present to the hazardous area)
Short-Circuit Current (Isc) 93 mA (Maximum current the barrier can deliver to the hazardous area)
Entity Approval Typically suitable for Group IIC hazardous gases.
Installation Must be installed in a safe area with a dedicated, certified IS earth ground (earth return) connection.
Wiring Simple two-wire connection (in-series with the signal line).
Housing Typically a blue plastic module for DIN rail mounting.
Technical Parameters
Category Specification
Model 22DILEM
Product Type Digital Input Expansion Module / Remote I/O Module
Number of Inputs 22 Discrete Inputs
Input Type 24V DC Sink/Source (PNP/NPN) universal inputs.
Input Voltage 24V DC (nominal)
Communication
Protocol Modbus RTU
Interface RS-485
Power Supply Requires a separate 24V DC power supply for the module and inputs.
Isolation Typically provides galvanic isolation between the communication bus, power supply, and input channels.
Status Indication LED indicators for power, communication, and status of each input channel.
Mounting Standard 35 mm DIN rail.
Key Features
Modular Expansion Easily expands the I/O count of a compatible Eaton PLC system.
Reduced Wiring Allows for distributed I/O architecture, saving wiring time and cost.
Configuration Typically configured via the master PLC or dedicated software, with the I/O mapping defined by the Modbus address.