Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, DILRC Series
Model Number DILRC-22
Rated Operational Current (Ie) 22 A (for AC-1 category, resistive loads)
Poles 4-Pole (Typically 4 Normally Open (NO) contacts)
Rated Operational Voltage (Ue) Up to 690V AC
Control Coil Voltage Available in multiple standard AC and DC voltages (e.g., 24V AC/DC, 110V AC, 230V AC, etc.). The specific voltage is not defined by "22" and must be specified when ordering.
Utilization Categories AC-1: Non-inductive or slightly inductive loads
AC-15: Control of electromagnetic loads (≤ 720 VA)
DC-1: Non-inductive or slightly inductive loads
DC-13: Control of electromagnetic loads
Mechanical Life ~ 10 - 30 million operations (typical for this series)
Electrical Life Varies by utilization category (e.g., ~ 1-3 million operations at rated AC-15 load)
Mounting Standard 35mm DIN Rail (EN 60715)
Standards Compliance IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14
Terminal Type Cage Clamp or Screw Clamp
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, NZM Series
Model Number NZMB1-4-A125
Rated Current 125 A (Frame Size)
Poles 4-Pole
Rated Operational Voltage (Ue) Up to 690V AC
Rated Insulation Voltage (Ui) 800V AC
Trip Unit Type Type A - Adjustable Electronic Trip Unit
Protection Functions L - Long-time Delay (Overload)
S - Short-time Delay (Short-Circuit)
I - Instantaneous (Short-Circuit)
Breaking Capacity (Icu) High interrupting capacity (e.g., 25kA, 35kA, or higher depending on specific rating and voltage)
Standards Compliance IEC 60947-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, NZM Series
Model Number NZMN1-A63
Rated Current 63 A (Frame Size)
Poles Typically 3-Pole (Pole configuration may vary, confirm with specific order code)
Rated Operational Voltage (Ue) Up to 690V AC
Rated Insulation Voltage (Ui) 800V AC
Trip Unit Type Type A - Adjustable Electronic Trip Unit
Protection Functions L - Long-time Delay (Overload)
S - Short-time Delay (Short-Circuit)
I - Instantaneous (Short-Circuit)
Breaking Capacity (Icu) High interrupting capacity (Typically 25 kA to 50 kA depending on specific voltage rating)
Standards Compliance IEC 60947-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, M22 Series
Model Number M22-PVT
Sensor Type Inductive Proximity Sensor
Housing Material Typically Nickel-plated brass or Stainless Steel
Thread Size M22 x 1.5
Connection Type PVC Cable (Specific length and conductor count vary - e.g., 2m 3-core)
Sensing Distance 5 mm (Standard for M22 inductive sensors)
Output Type DC 3-wire (Typically PNP or NPN, selectable or fixed - check datasheet)
Supply Voltage 10-30V DC
Rated Operating Current Typically ≤ 200 mA
Switching Frequency Typically ≤ 500 Hz
Protection Degree IP67
Standards Compliance IEC 60947-5-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, DILM Series
Model Number DILM9-10
Rated Operational Current (Ie) 9 A at AC-3, 400V
Thermal Current (Ith) 9 A
Poles (Main Circuit) 3 (Normally Open)
Auxiliary Contacts 1 NO (Normally Open) + 1 NC (Normally Closed) - Convertible
Rated Operational Voltage (Ue) Up to 690V AC
Control Coil Voltage Available in multiple standard AC voltages (e.g., 24V, 110V, 230V, 400V AC). The specific voltage must be specified when ordering.
Utilization Categories AC-3: Squirrel cage motors: Starting, switching off during running
AC-1: Non-inductive or slightly inductive loads
Motor Rating (at 400V AC) 4 kW / 5.5 HP
Mechanical Life ~ 15 million operations
Electrical Life (AC-3) ~ 1.5 million operations
Mounting Standard 35mm DIN Rail (EN 60715) or screw mounting
Standards Compliance IEC/EN 60947-4-1, UL 508, CSA C22.2 No. 14
Terminal Type Cage Clamp / Screw Clamp
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, ETR4 Series
Model Number ETR4-70-A
Poles 3-Pole
Trip Class Class 10
Current Setting Range 53 - 70 A
Rated Operational Voltage (Ue) 690V AC
Rated Insulation Voltage (Ui) 1000V AC
Ambient Temperature Range -25°C to +60°C (Derating may apply above +50°C)
Standards Compliance IEC/EN 60947-4-1, UL 508, CSA C22.2 No. 14
Mounting Snap-on mounting to compatible Eaton DIL contactors
Auxiliary Contacts 1 NO (95-96) + 1 NC (97-98) - Convertible
Reset Mode Manual reset (Automatic reset optional)
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, DILM Series
Model Number DILM65C
Rated Operational Current (Ie) 65 A at AC-3, 400V
Thermal Current (Ith) 65 A
Poles (Main Circuit) 3 (Normally Open)
Auxiliary Contacts Typically 1 NO (Normally Open) - Fixed (configurable with additional blocks)
Rated Operational Voltage (Ue) Up to 690V AC
Control Coil Voltage "C" denotes a standard DC voltage range. The specific voltage must be ordered (e.g., 24V DC, 110V DC).
Utilization Categories AC-3: Squirrel cage motors: Starting, switching off during running
AC-1: Non-inductive or slightly inductive loads
Motor Rating (at 400V AC) 37 kW / 50 HP
Mechanical Life ~ 10 million operations
Electrical Life (AC-3) ~ 1 million operations
Mounting Standard 35mm DIN Rail (EN 60715) or screw mounting
Standards Compliance IEC/EN 60947-4-1, UL 508, CSA C22.2 No. 14
Terminal Type Screw Clamp
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, M22 Series
Model Number M22-R4K7
Sensor Type Inductive Proximity Sensor
Housing Material Typically Nickel-plated brass or Stainless Steel
Thread Size M22 x 1.5
Connection Type Pre-wired cable (Specific length varies)
Integrated Resistor 4.7 kΩ
Sensing Distance 5 mm (Standard for M22 inductive sensors)
Output Type Analog or Special Configuration
Supply Voltage 10-30V DC
Protection Degree IP67
Standards Compliance IEC 60947-5-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, NZM Series
Model Number NZMN2-A200
Number of Poles 2-Pole
Rated Current 200 A (Frame Size)
Rated Operational Voltage (Ue) Up to 480V AC
Rated Insulation Voltage (Ui) 690V AC
Rated Ultimate Breaking Capacity (Icu) Typically 25 kA / 35 kA at 480V AC (Confirm with specific datasheet)
Trip Unit Type Type A - Adjustable Electronic Trip Unit
Protection Functions L - Long-time Delay (Overload)
S - Short-time Delay (Short-Circuit)
I - Instantaneous (Short-Circuit)
Standards Compliance IEC 60947-2
Technical Parameters
Parameter Category Description / Value
Brand & Series Eaton, EMT6 Series
Model Number EMT6-K
Power Supply Voltage 24-240V AC/DC (Wide range, auto-sensing)
Output Relay DPDT (2 CO) - 2 Changeover contacts
Contact Rating: Typically 8A @ 250V AC
Timing Ranges Multiple ranges selectable (e.g., from 0.05 seconds up to 100 hours)
Functions Specific set of timing functions selectable (e.g., On-delay, Off-delay, Interval, Flasher, etc. - defined by the "K" variant)
Accuracy ±0.5% of set time ± 20 ms (typical for digital timers)
Mounting DIN Rail (35mm)
Display / Indication LED Status Indicators (Power, Output state)
Standards Compliance IEC/EN 61812-1, UL 508, CSA C22.2 No. 14