Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZMX
Product Model IZMX16N3-V12W
Product Type Molded Case Circuit Breaker (MCCB) with Electronic Trip Unit
Number of Poles 3 Poles
Rated Operational Voltage (Ue) 400 V AC (50/60 Hz)
Frame Size (Iu) 160 A
Rated Current (In) Adjustable, up to 160 A
Rated Ultimate Breaking Capacity (Icu) at 415V 36 kA (IEC 60947-2)
Trip Unit Type V12W Electronic Trip Unit
Protection Functions Long-time delay (L), Short-time delay (S), Instantaneous (I), Ground-fault (G)
Measurement Functions Current, Voltage, Power, Energy, Power Factor, Frequency
Communication Supports optional communication modules (e.g., for Modbus)
Display LCD display for parameter setting and measurement reading
Mounting Fixed Installation
Standards IEC 60947-2
Technical Parameters Parameter Category Specification / Value
Brand Eaton
Product Series IZMX
Product Model IZMX16H44-V16W
Product Type 4-Pole Molded Case Circuit Breaker (MCCB) with Electronic Trip Unit
Number of Poles 4 Poles (3 Poles + Neutral)
Rated Operational Voltage (Ue) 400 V AC (50/60 Hz)
Frame Size (Iu) 160 A
Rated Current (In) Adjustable, up to 160 A
Rated Ultimate Breaking Capacity (Icu) at 400V 36 kA (IEC 60947-2, typical value for this frame)
Trip Unit Type V16W Electronic Trip Unit
Protection Functions Long-time delay (L), Short-time delay (S), Instantaneous (I), Ground-fault (G)
Measurement Functions Current, Voltage, Power, Energy, Power Factor, Frequency, Harmonics
Communication Supports optional communication modules (e.g., for Modbus)
Display LCD display for parameter setting and measurement reading
Mounting Fixed Installation
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM91
Product Model IZM91N3-U06W
Product Type Draw-Out Air Circuit Breaker (ACB)
Number of Poles 3 Poles
Rated Operational Voltage (Ue) 690 V AC
Frame Size (Inm) 630 A
Rated Current (Iu) 630 A (Adjustable via trip unit)
Rated Ultimate Breaking Capacity (Icu) at 415V 65 kA (IEC 60947-2)
Trip Unit U06W (Advanced Electronic Trip Unit)
Protection Functions Long-time, Short-time, Instantaneous, Ground Fault
Measurement & Monitoring Current, Voltage, Power, Energy, Power Factor, Frequency, Harmonics (THD)
Communication Protocols Embedded Ethernet (Modbus TCP), RS-485 (Modbus RTU)
Mounting Style Draw-Out (in compatible fixed mounting frame)
Display Graphical LCD Display
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM91
Frame Size (Inm) 630 A
Rated Operational Voltage (Ue) 690 V AC
Number of Poles 3 or 4 Poles (depending on specific model)
Rated Ultimate Breaking Capacity (Icu) at 415V 65 kA (IEC 60947-2)
Mounting Style Fixed or Draw-Out (depending on specific model)
Typical Trip Unit Options • Fixed Thermal-Magnetic (Non-adjustable)
• Electronic Trip Unit (e.g., V06C, U06W - adjustable protection, measurement, communication)
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM N2
Product Model IZMN2-V3200-AV
Product Type Vacuum Circuit Breaker (VCB)
Number of Poles 2 Poles
Rated Voltage 12/17.5 kV (or similar, specific to medium-voltage range)
Rated Current 3200 A
Rated Short-Time Withstand Current (Icw) High (e.g., 40 kA or 50 kA for 3s, specific value depends on design)
Rated Breaking Current High (commensurate with its rating)
Trip Unit V3200 (Electronic Trip Unit)
Interruption Technology Vacuum
Control Voltage 125 V DC (Common for station battery systems)
Mounting Fixed in metal-clad switchgear
Standards IEC 62271-100
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM91
Frame Size (Inm) 1600 A
Rated Operational Voltage (Ue) 690 V AC
Number of Poles 3 or 4 Poles (depending on specific model)
Rated Ultimate Breaking Capacity (Icu) at 415V 65 kA (IEC 60947-2)
Mounting Style Draw-Out (typical for this frame size)
Typical Trip Unit Options Electronic Trip Unit (e.g., V16F, V16W - adjustable protection, measurement, communication)
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series IZM97
Product Model IZM97B4-U08W
Product Type Fixed Mounted, 4-Pole Air Circuit Breaker (ACB)
Number of Poles 4 Poles (3 Poles + Neutral)
Rated Insulation Voltage (Ui) 1000 V AC
Rated Operational Voltage (Ue) 690 V AC
Frame Size (Inm) 3200 A
Rated Current (Iu) 3200 A (Adjustable via trip unit)
Rated Ultimate Breaking Capacity (Icu) at 415V 150 kA (IEC 60947-2)
Trip Unit U08W (Advanced Electronic Trip Unit)
Protection Functions Long-time, Short-time, Instantaneous, Ground Fault
Measurement & Monitoring Current, Voltage, Power, Energy, Power Factor, Frequency, Harmonics (THD)
Communication Protocols Embedded Ethernet (Modbus TCP), RS-485 (Modbus RTU)
Mounting Fixed Installation in Switchboard
Display Graphical LCD Display
Standards IEC 60947-2
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series EASY
Product Model EASY209-SE
Product Type Soft Starter with integrated Bypass
Rated Operational Voltage 208-575 V AC, 50/60 Hz
Motor Power Rating (at 400V) 9 A (Approx. 4 kW / 5 HP)
Maximum Current 12 A
Control Method Voltage ramp control with adjustable starting voltage and ramp time.
Key Features • Integrated Bypass Contactor
• Adjustable Start Voltage & Ramp Time
• Adjustable Soft Stop (deceleration)
• Overload Protection
• Phase Imbalance Protection
Control Connections Screw terminals for Start/Stop control and relay outputs.
Status Indication LED indicators for Power, Run, and Bypass.
Mounting DIN Rail Mounting (35 mm)
Approvals / Certifications CE, cULus
Technical Parameters Parameter Category Specification / Value
Brand Eaton
Product Series P5
Product Model P5-160-V/SVB
Product Type Switched-Mode Power Supply (SMPS) with Static Voltage Buffer
Output Power 160 W
Output Voltage 24 V DC
Rated Output Current 6.7 A
Input Voltage Range 85...264 V AC (wide range) / 120...370 V DC
Input Frequency 47...63 Hz
Key Feature Static Voltage Buffer (SVB) - Holdup time typically ≥ 20 ms after mains failure
Efficiency High efficiency (typically > 93%)
Mounting DIN Rail Mounting (35 mm)
Connection Removable screw terminal block
Operating Temperature -25 °C ... +70 °C (with derating)
Approvals / Certifications CE, cULus, ATEX (for specific hazardous area applications)
Technical Parameters
Parameter Category Specification / Value
Brand Eaton
Product Series DILM
Product Model DILM32-XTEE11
Product Type Contactor Relay (4-pole, changeover contacts) with Latching Function
Number of Main Contacts 4
Contact Type 4 Changeover (CO) / Form C (Each contact: 1 NO + 1 NC)
Rated Operational Current (Ith) 10 A (e.g., at 230V AC)
Rated Insulation Voltage (Ui) 690 V AC
Control Coil Voltage 24 V DC
Special Feature Latching (Impulse) Version (Mechanically held)
Electrical Life > 1 x 10⁶ operations
Mechanical Life > 10 x 10⁶ operations
Mounting 35 mm DIN Rail
Terminal Type Cage Clamp (Spring-loaded)
Auxiliary Contacts Integrated (as part of the "11" configuration)
Approvals / Certifications CE, cULus, CCC, IEC/EN 60947-5-1