Technical Specifications
Parameter Category Specification
Ordering & General Data
Order No. 1318220000
Type ACT20X-HUI-SAO-LP-S
Version ACT20X, EX signal isolating converter, 1-channel version, Output-loop powered
GTIN (EAN) 4050118323955
Qty. 1 pc(s)
Delivery Status Discontinued
Dimensions & Weight
Width 12.5 mm / 0.492 inch
Height 117.2 mm / 4.614 inch
Depth 113.6 mm / 4.472 inch
Net Weight 125 g
Input (Ex / Intrinsically Safe)
Number of Inputs 1
Input Type RTD (2-/3-/4-wire), Thermocouple (TC), DC current, DC voltage, Resistance, Potentiometer
Supported RTDs PT10, PT20, PT50, PT100, PT250, PT300, PT400, PT500, PT1000, Ni50, Ni100, Ni120, Ni1000
Supported TCs B, E, J, K, N, R, S, T (IEC 60584-1); L, U (DIN43710)
Input Current Configurable: ±25 mA, 0...20 mA, 4...20 mA
Input Voltage Configurable: ±12 V, ±28 V, ±600 mV, ±150 mV
Input Resistance (Current) 70 Ω
Input Resistance (Voltage) >10 MΩ @ 600 mV, 2 MΩ @ 28 V
Potentiometer 1.2…500 kΩ
Sensor Supply 28…16.5 V DC / 0…20 mA
Temperature Input Range Configurable -200...+800°C
Output
Number of Outputs 1
Output Signal 4...20 mA (max. 23 mA)
Load Impedance ≤ 700 Ω
Output Type Output-loop powered
General Specifications
Supply Voltage via output current loop, 11...28 V DC (loop powered)
Power Consumption ≤ 3.5 W
Accuracy <0.1 % of end value
Step Response Time 250 ms (10…90%)
Temperature Coefficient <0.02 °C of measuring range / °C
Protection Degree IP20