Technical Parameters
Parameter Category Specification Details
General Model EU5C-SWD-DP Form 4S, Three-Phase, 4-Wire Meter with Advanced Features ("DP")
Product Line Eaton Crouse-Hinds Series / Power Xpert Metering
Electrical Characteristics
System Type Three-Phase, 4-Wire (3P4W - Wye)
Rated Voltage 347/600V AC (Line-to-Line)
Current Input Via external Current Transformers (CTs). Common secondary ratings: 5A or 1A.
Frequency 50/60 Hz
Measurement Capabilities
Basic Parameters Volts (L-N, L-L), Amps, Frequency, Real/Reactive/Apparent Power (kW, kvar, kVA), Power Factor, Demand (kW, kVA, A)
Energy Import/Export kWh, kvarh
Power Quality Total Harmonic Distortion (THD) for V & I, Individual Harmonics, Min/Max/Average recordings, Sag/Swell detection.
Communication
Communication Ports The "DP" variant typically includes multiple ports, often an Ethernet port and a RS-485 serial port.
Protocols Commonly supports Modbus TCP/IP (over Ethernet), BACnet IP (over Ethernet), and Modbus RTU (over RS-485).
Display Integrated backlit LCD, often graphical.
Accuracy
Standard ANSI C12.20 Class 0.2 (Revenue Grade)
Voltage & Current ±0.1% of Reading
Power & Energy ±0.2% of Reading
Physical & Environmental
Mounting Hardwired installation into a dedicated meter socket within an Eaton enclosure.
Operating Temperature -40°C to +70°C (-40°F to +158°F)