Parameter Specification
Product Series Eaton DS7 / XStart
Model Number DS7-340SX007N0-N
Description Soft Starter, 34A, 15kW @ 400V
Rated Supply Voltage 400V AC, 50/60 Hz
Motor Power Rating 15 kW / 20 HP @ 400V
Rated Current 34 A
Current Range 5 - 34 A (Adjustable)
Max. Current 150 A (for 1 second)
Control Method Voltage Ramp, Current Limit
Integrated Bypass Yes (Internal Bypass Contactor)
Control Voltage 100-250V AC, 50/60 Hz (from factory, as denoted by 'SX')
Control Connections Screw Terminals
Start Time Adjustment 1 - 30 seconds (Adjustable)
Torque Control Adjustable Initial Torque (Kickstart) and Torque Limit
Protection Features Overload, Phase Loss, Phase Imbalance, Locked Rotor, Overheating, Jogging Protection
Status Indication LED Indicators for Power, Run, Bypass, Fault
Communication Optional communication modules (e.g., Profibus, DeviceNet) available
Enclosure Rating IP00 (Open Type, must be installed in a control panel for protection)
Standards & Certifications CE, UL, cUL, RoHS
More details >>