Technical Specifications
Parameter Category Specification
Ordering & General Data
Order Number 2456180000
Type ACT20X-HTI-SAO-P
Version EX signal isolating converter, Ex-input: I,ϑ, Safe-output: 4-20mA, 1-channel
GTIN (EAN) 4050118471595
Quantity 1 pc(s)
Dimensions & Weight
Width 22.5 mm / 0.886 inch
Height 127.3 mm / 5.012 inch
Depth 114.6 mm / 4.512 inch
Net Weight 178 g
Input (Ex / Intrinsically Safe)
Number of Inputs 1
Input Type RTD (2-/3-/4-wire), Thermocouple (TC), DC current (mA)
Supported RTDs PT10, PT20, PT50, PT100, PT250, PT300, PT400, PT500, PT1000, Ni50, Ni100, Ni120, Ni1000
Supported TCs B, E, J, K, N, R, S, T (IEC 60584-1); L, U (DIN43710)
Input Current (mA) 0...20 mA, 4...20 mA
Input Resistance (Current) 20 Ω + PTC 50 Ω
Line Resistance (Measuring Circuit) ≤ 50 Ω
Temperature Input Range Configurable, e.g., PT100: -200…+850 °C, K: -180…+1372 °C, B: +100…+1820 °C
Output
Number of Outputs 1
Output Signal 0/4...20 mA (configurable)
Output Type Active (current source) or passive (current sink)
Load Impedance (Current) ≤ 600 Ω
Output Current Range 0…23 mA, configurable: 0…20 / 4…20 / 20…0 / 20…4 mA
Error Output Signal Configurable: downscale (3.5 mA) / upscale (23 mA)
Status Output (Alarm)
Type Status relay, 1 NC (voltage-free)
Alarm Functions Line interruption, short circuit, no supply voltage, device error
Nominal Switching Voltage (Safe Area) ≤ 125 V AC / 110 V DC
Continuous Current (Safe Area) ≤ 0.5 A AC / 0.3 A DC
General Specifications
Supply Voltage 19.2…31.2 V DC
Power Consumption ≤ 0.8 W
Protection Degree IP20
Connection Type PUSH IN
Wire Gauge (AWG) AWG 26...14
Configuration Via FDT/DTM software, requires CBX200 USB adapter (8978580000)
Step Response Time ≤ 400 ms (current), ≤ 1 s (temperature)
Environment
Operating Temperature -20 °C...60 °C
Storage Temperature -20 °C...85 °C
Humidity 0...95 % (no condensation)
Safety & Approvals
Safety Integrity Level (SIL) SIL 2 (per IEC 61508)
ATEX/IECEx Marking II (1) G [Ex ia Ga] IIC/IIB/IIA; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I
Installation Location Safe area, Zone 2
Ex Parameters (U0/I0/P0) 8.7 V DC / 18.4 mA / 40 mW
Insulation Voltage 2.6 kV (input/output)
Certificates cULus (E337701)