Parameters / Specifications
Model: FS‑67CFR‑224
Series: 67C Series Instrument Supply Regulators
Type: Direct‑operated regulator with integral filter and internal relief valve
Body Material: Aluminum alloy
End Connections: ¼ inch NPT inlet and outlet
Maximum Inlet Pressure: 250 psig (≈ 17.2 bar)
Outlet (Regulated) Pressure Range: 0‑35 psig (≈ 0‑2.4 bar)
Maximum Emergency Outlet Pressure: 50 psig (≈ 3.4 bar) above setpoint
Filter: Integral, for particulate removal
Internal Relief Valve: Yes, for downstream protection
Temperature Capability:
Nitrile (NBR): –40 °F to +180 °F (≈ –40 °C to +82 °C)
Fluoroelastomer (FKM): 0 °F to +300 °F (≈ –18 °C to +149 °C)
Silicone (VMQ): –60 °F to +180 °F (≈ –51 °C to +82 °C)
Approximate Weight: ~0.5 kg
Media / Application: Clean air or compatible gases for instrumentation or pneumatic systems
Features:
Compact and lightweight construction
Panel or inline mounting
Replaceable filter element
Soft‑seat relief valve prevents over‑pressure and leakage
Durable construction suitable for long-term instrumentation service
Specifications / Parameters
Model: HSR‑CHGBLYN
Regulator type: Pressure reducing regulator, direct‑acting, with internal relief
Body material: Cast iron
End connections: 1″ NPT inlet/outlet (globe body style)
Maximum operating inlet pressure: 125 psig (≈8.6 bar)
Maximum emergency inlet pressure: 150 psig (≈10.3 bar)
Outlet (regulated) pressure range: 12.5 to 20 inches w.c. (approx. 31 to 50 mbar) for one spring range; other available spring ranges include 4‑6” w.c., 6‑8” w.c., 8‑10” w.c., 10‑12.5” w.c., 12.5‑20” w.c., 20‑35” w.c., and 1.25‑2.2 psig (0.09‑0.15 bar)
Maximum allowable outlet pressure differential (to avoid internal part damage): approx. 3 psig (≈0.21 bar) above setpoint
Temperature capability: approx. –20 °F to +160 °F (≈ –29 °C to +71 °C)
Orifice size / capacity guidelines: for orifice sizes from 1/8″ to 1/2″, the maximum operating inlet pressures vary (for example for a 1/8″ orifice: 125 psig / 8.6 bar; for a 1/2″ orifice: ~20 psig / 1.4 bar)
Typical weight: ~4 lb (≈2 kg)
Application: Fuel‑gas supply regulation in residential, multi‑dwelling, commercial or light industrial installations, meeting or exceeding ANSI B109.4 / CGA 6.18 standards.
Parameters / Specifications
Model: Fisher 67CFR‑225 (and implied option suffix “/C4”)
Series: Fisher 67C Series Instrument Supply Regulators
Construction / Type: Filtered regulator with internal relief (integral filter + internal relief)
Body Material: Aluminum alloy (standard for 67C/67CF/67CFR)
Connections / Body Size: ¼ inch NPT (inlet and outlet)
Maximum Inlet Pressure (Body Rating): 250 psig (≈ 17.2 bar)
Outlet (Regulated) Pressure Range (spring range for “‑225”): 0–60 psig (≈ 0–4.1 bar)
Maximum Emergency Outlet Pressure (i.e., the built‑in relief will relieve when outlet exceeds setpoint by this margin): 50 psig (≈3.4 bar) above outlet setting
Filter: Integral 5‑micron polyethylene (standard) filter included
Temperature Capability (depending on elastomer / filter material):
NBR (nitrile) elastomers: approx –40 °F to +180 °F (≈ –40 °C to +82 °C)
FKM (fluoroelastomer) elastomers: approx 0 °F to +300 °F (≈ –18 °C to +149 °C)
VMQ (silicone) diaphragm with low‑temperature bolting: approx –60 °F to +180 °F (≈ –51 °C to +82 °C)
Approximate Weight: ~1 lb (≈0.5 kg)
Media / Typical Use: Air or compatible clean gases, for pneumatic instrumentation, controllers, panel‑mounted systems, regulators supplying instrument air.
Parameters / Specifications
Model: Fisher 167DA‑11
Series: Fisher 167D Series Switching Valves
Type: Three‑way switching valve (Ports A and C are main flow paths; Port B and control/vent Port D as described)
Body Size / End Connections: Ports A and C: ¼ in or ½ in NPT; Ports B and D: ¼ in NPT
Maximum Inlet (Body) Pressure: 125 psig (≈ 8.6 bar) for standard 167DA configurations
Set Pressure (Control Spring Range): One of the available spring ranges for 167DA series (for example 14‑20 psig, 16‑35 psig, 25‑60 psig, 40‑125 psig) — the “‑11” suffix corresponds to one of these, detailed value should be checked in the ordering code
Temperature Capability (Standard Service): ‑20 °F to +180 °F (≈ ‑29 °C to +82 °C) for standard construction; low‑temperature service or high‑temperature service versions available
Approximate Weight: ~1.2 lb (≈0.5 kg)
Flow / Sizing Coefficient (Wide‑Open): For ¼ in NPT version: Cv ≈ 30.58; for ½ in NPT version: Cv ≈ 32.22
Application: Switching pneumatic control signals, instrument air systems, diverting flow in control circuits, actuation logic for pneumatic systems
Parameters / Specifications
Model: Fisher 289H‑41
Series: Fisher 289 Series Relief / Back‑Pressure Regulators
Body Size / End Connections: 1″ NPT (inlet & outlet) for the “H” size version
Relief (Set) Spring Range: Approx 1.0 to 4.5 psig (≈0.07 to 0.31 bar) for the “‑41” variant
Maximum Allowable Inlet Pressure (Body Rating): Approx 100 psig (≈6.9 bar) for this body size
Temperature Capability (depending on elastomer):
Nitrile (NBR) / Neoprene (CR): –20 °F to +150 °F (≈ –29 °C to +66 °C)
Fluoroelastomer (FKM): 20 °F to +300 °F (≈ –7 °C to +149 °C) (available on “H/HH” types)
Approximate Weight: ~4 lb (≈2.0 kg) for the 1″‑NPT size “H” body
Media / Application: Non‑corrosive gas or air service, used as a relief device or back‑pressure regulator in downstream systems to limit pressure, reduce pressure surges, protect equipment
Features:
Spring‑loaded throttling action with minimal pressure surge during relief
Compact design for installation where space may be limited
Reliable, relatively simple construction for high dependability
Parameters / Specifications
Model: 667‑46i
Actuator Type: Spring‑opposed diaphragm actuator, reverse‑acting
Series: Fisher Type 667
Size: 46i diaphragm class
Travel (Maximum Stroke): Up to 76 mm (~3.0 in) standard; up to 102 mm (~4.0 in) for extended stroke versions
Signal Pressure Range: Typical 3‑15 psig (0.2‑1.0 bar) or 6‑30 psig (0.4‑2.0 bar)
Operating Temperature Range: Standard –58 °F to +180 °F (–50 °C to +82 °C) depending on diaphragm material and configuration
Construction Materials: Cast iron/steel body, molded diaphragm, heavy‑duty spring case
Features:
Integral mounting pad for digital valve positioners
High thrust capability, linear response
Optional manual handwheel, travel stops, and low-temperature variants
Typical Applications: Sliding‑stem control valves, industrial process control requiring failsafe action and precision response
Fail State: Spring drives actuator to fail position (commonly closed) on loss of supply signal
Approximate Weight: Varies with size and accessories; typically tens of pounds (kilograms)
Parameters / Specifications
Model: 667/EZ
Actuator Type: Spring‑opposed diaphragm actuator, reverse‑acting
Series: Fisher Type 667 Diaphragm Actuators
Sizes: Multiple sizes available (e.g., 30, 34, 40, 45, 46, 50, 60, 70, 76, 87) to match various valve applications
Signal Pressure Range: Typical 3‑15 psig (0.2‑1.0 bar) or 6‑30 psig (0.4‑2.0 bar), depending on configuration
Fail Action: Reverse‑acting (spring drives actuator to fail position when signal is lost)
Diaphragm Travel / Stroke: Up to ~100 mm (4 in) depending on size
Construction Materials: Cast iron/steel body and spring case; high-strength diaphragm; heavy-duty construction for durability and corrosion resistance
Operating Temperature Range: Standard and low-temperature service versions; low-temperature service down to approx –58 °F (–50 °C)
Applications: On/off or throttling operation of industrial control valves in chemical, petrochemical, power generation, and oil & gas industries
Features:
Integral mounting pad for valve positioners
Internal air passage for improved actuator response
Optional manual handwheel and travel stops
Flexible size range and configurations for various valve applications
Technical Specifications
Category Specification
Model 67CS-413
Type Direct-Acting, 3-Way (3/2) Solenoid Valve
Operation Single Solenoid, Spring-Return
Standard Function Likely Normally Closed (NC) or a similar specific flow path. Must be confirmed with datasheet.
Port Size Typically 1/4" NPT
Media Clean, dry, lubricated or non-lubricated air.
Maximum Supply Pressure Typically 150 psig (10.3 bar).
Voltage / Electrical Connection Available in various standard voltages (e.g., 24 VDC, 120 VAC). Defined by the specific coil ordered.
Enclosure Rating Typically NEMA 4X (IP65) for weatherproof and corrosion-resistant protection.
Body Material Brass or Stainless Steel.
Seal Material Buna-N (Nitrile) is standard.
Technical Specifications
Category Specification
Model Y690AM
Type Pneumatic Spring-Diaphragm Actuator (Specifically, a Piston-Type for Rotary Valves)
Action Reverse Action (A) & Double-Acting (M)
• Reverse Action: Stem retracts with increasing air signal.
• Double-Acting: Requires air pressure to both open and close the valve. It has no spring and is not fail-safe.
Standard Air Signal 3 to 15 psig (0.2 to 1.0 bar)
Supply Air Pressure Maximum 100 psig (6.9 bar) supply pressure. The actual torque output is directly proportional to the supply pressure used.
Travel Standard travel is 90 degrees of rotation, suitable for quarter-turn valves.
Mounting Designed for direct mounting to Fisher V100, V150, V500, and other compatible rotary valve series via a standardized bracket.
Typical Torque Output The Y690A size provides a specific torque range. For precise torque values at different air pressures, you must consult the official Fisher torque chart. (e.g., With 100 psig air supply, the torque output can be in the range of several hundred lb-in).
Diaphragm / Piston Material Nitrile (Buna-N) is standard for elastomers.
Housing Material Cast aluminum or ductile iron, with a corrosion-resistant coating.
Temperature Limits Standard elastomers are suitable for temperatures between -20° to +180°F (-29° to +82°C).
Technical Specifications
Category Specification
Model Type 67DS
Type Pneumatic Differential Pressure Switch
Function To provide an electrical contact based on a pre-set pressure point.
Sensing Element Diaphragm or Piston
Switch Action Single Pole, Double Throw (SPDT) snap-action switch is common.
Pressure Ranges Available in various adjustable ranges (e.g., 3-15 psig, 5-50 psig, etc.).
Differential (Deadband) Adjustable.
Electrical Rating Typical for industrial control circuits (e.g., 10A @ 125/250 VAC).
Enclosure Rating Typically NEMA 4X (IP65) for weatherproof and corrosion-resistant protection.
Process Connection Typically 1/4" NPT
Materials of Construction Body: Die-cast Aluminum or Fiberglass.
Wetted Parts: Brass, Stainless Steel.
Ambient Temperature Limit Standard: -20°F to +150°F (-29°C to +66°C).