Products
Products
home
NSX160N 4P 160A 2.2

The Schneider Electric Masterpact NSX160N is a four-pole, 160A molded case circuit breaker (MCCB) from the premium Masterpact NSX range. The "N" suffix indicates its Standard breaking capacity, and it is equipped with a Micrologic 2.2 electronic trip unit.

open
TEL:+86 13600179521
Mail:info@hongkongeasy.com
info@hongkongeasy.com
WhatsApp
Parameters
Request a Quote
Return to List
Parameters: Parameter Value / Description Product Line / Frame Size Masterpact NSX160 Rated Current (In) 160 A (Set and protected by the installed Micrologic 2.2 trip unit). Number of Poles 4 (L1, L2, L3, N). The specific configuration (e.g., 4P4D or 4P3D) determines if the neutral is fully protected or only switched. Breaking Capacity Standard (N Rating). Rated Ultimate Breaking Capacity (Icu) Typically 50 kA at 415V AC (IEC 60947-2). (Confirm for specific voltage). Rated Service Breaking Capacity (Ics) 100% of Icu (IEC 60947-2). Rated Operational Voltage (Ue) Up to 690 V AC Trip Unit Micrologic 2.2 Electronic Trip Unit. • Protection Functions: Long-time (L), Short-time (S), Instantaneous (I). Ground fault (G) protection is NOT included in the standard 2.2 unit. • Features: Basic load monitoring (current display), adjustable protection settings for L, S, I. Communication Not embedded. Can be optionally equipped with a separate communication module (e.g., OFC, CBE) for integration. Standard IEC 60947-2 Mounting Withdrawable (standard racking mechanism) or Fixed. Connection Front or Rear (depends on the kit). Width Approx. 168 mm (for a 4-pole withdrawable unit).