Parameter Specification
Product Series Eaton PowerXL DG1 (S811 Line)
Model Number S811+N66N3S
Description Variable Frequency Drive, 128A, 75kW, 400V
Rated Input Voltage 380 - 480V AC, 3-Phase, 50/60 Hz
Rated Output Current 128 A
Motor Power Rating 75 kW (100 HP) @ 400V
Overload Capacity 150% of rated current for 60 seconds
Control Methods V/F Control, Sensorless Vector Control
Integrated Features DC Bus Choke (Standard), EMC Filter (Standard), Removable Graphic Keypad
Digital Inputs 4 (programmable)
Digital Outputs 2 (1 relay, 1 transistor)
Analog Inputs 2 (0/4-20mA or 0-10V, programmable)
Analog Output 1 (0/4-20mA or 0-10V, programmable)
Communication Protocols Modbus RTU (standard). Optional fieldbus cards (e.g., Profibus DP, DeviceNet, EtherNet/IP, PROFINET)
Enclosure Rating IP20 / UL Type Open (Designed for mounting inside a control panel)
Standards & Certifications CE, cULus, RoHS
Parameter Specification
Product Series Eaton CPY C3 Series
Model Number CPY-C3-AAL41-HD
Description Definite Purpose Contactor, 3-Pole, 40A, Heavy Duty
Rated Load 40 Amps
Poles 3
Rated Voltage 240V AC / 480V AC / 600V AC
Rated Load (at 240V AC) Inductive (AC-3 - Motor): 25 HP
Resistive (AC-1): 40A
Coil Voltage 240V AC (This is a critical part of the model number "AAL*41*")
Terminals Screw Terminals (for both power and coil)
Electrical Life Higher than standard duty models, suitable for frequent switching (e.g., 500,000+ mechanical operations, 100,000+ electrical at rated load).
Mounting DIN Rail or Panel Mount
Agency Approvals UL 508, CSA C22.2 No. 14, CE
Parameter Specification
Product Series Eaton CPY C3 Series
Model Number CPY-C3-ADV151
Description Definite Purpose Contactor, 2-Pole, 30A
Rated Load 30 Amps
Poles 2
Rated Voltage 240V AC / 480V AC
Rated Load (at 240V AC) Resistive: 30A
Inductive (AC-3 - Motor): 25 HP
Inductive (AC-1): 30A
Ballast (Lighting): 20A
Coil Voltage 24V AC (This is a critical part of the model number "ADV*151*")
Terminals Screw Terminals (for both power and coil)
Mechanical Life Typically 1-2 million operations
Electrical Life Typically 100,000 - 200,000 operations at rated load
Mounting DIN Rail or Panel Mount
Agency Approvals UL 508, CSA C22.2 No. 14, CE
Parameter Specification
Product Series Eaton DS7
Model Number DS7-340SX070NO-L
Description Soft Starter with Bypass, 340A, 250kW, 400V, 24V Control, LCD Keypad
Rated Supply Voltage 400V AC, 50/60 Hz (3 Phase)
Motor Power Rating 250 kW (355 HP) @ 400V
Rated Current 340 A
Current Range Adjustable
Control Supply Voltage 24V AC/DC (as set by "SX" code)
Integrated Bypass Yes (Internal Bypass Contactor)
Keypad Advanced LCD Display (as denoted by -L)
Start Control Voltage ramp, Current limit, Torque control
Protection Features Overload, Phase Loss, Phase Imbalance, Locked Rotor, Overheating, Undercurrent
Communication Optional communication modules (e.g., Profibus DP, DeviceNet, Modbus RTU)
Enclosure Rating IP00 (Open Type, must be installed in a control panel)
Standards & Certifications CE, cULus, RoHS
Parameter Specification
Product Series Eaton PowerXL DG1 (S811 Line)
Model Number S811+T24P3S
Description Variable Frequency Drive, 24A, 7.5kW, 240V
Rated Input Voltage 200 - 240V AC, ±10%, 3-Phase, 50/60 Hz
Rated Output Current 24 A
Motor Power Rating 7.5 kW (10 HP) @ 240V
Overload Capacity 150% of rated current for 60 seconds
Control Methods V/F Control, Sensorless Vector Control
Integrated Features EMC Filter (Standard), Removable Graphic Keypad
Digital Inputs 4 (programmable)
Digital Outputs 2 (1 relay, 1 transistor)
Analog Inputs 2 (0/4-20mA or 0-10V, programmable)
Analog Output 1 (0/4-20mA or 0-10V, programmable)
Communication Protocols Modbus RTU (standard). Optional fieldbus cards (e.g., Profibus DP, DeviceNet, EtherNet/IP)
Enclosure Rating IP20 / UL Type Open (Designed for mounting inside a control panel)
Standards & Certifications CE, cULus, RoHS
Parameter / Specification Description
Product Type Replacement Control Printed Circuit Board (PCB)
Model Number PCB-DS7-200A-CONTROL-V05
Compatible With Eaton DS7 Series Soft Starters, 200A Frame Size
Core Function Executes soft start/stop control logic, provides motor protection, and handles user interface.
Protected Functions Typically includes overload, phase loss, phase imbalance, locked rotor, and over-temperature protection.
User Interface Connects to and controls the DS7 soft starter's built-in keypad and display.
Control Connections Manages the control wiring terminals for Run/Stop, fault reset, relay outputs, etc.
Firmware Comes pre-loaded with the operating firmware for the soft starter.
Usage Spare part for repair and maintenance. Must be installed by a qualified technician.
Parameter Specification
Product Series Eaton PowerXL DG1 (S811 Line)
Model Number S811+T30N3S
Description Variable Frequency Drive, 59A, 30kW, 400V
Rated Input Voltage 380 - 480V AC, 3-Phase, 50/60 Hz
Rated Output Current 59 A
Motor Power Rating 30 kW (40 HP) @ 400V
Overload Capacity 150% of rated current for 60 seconds
Control Methods V/F Control, Sensorless Vector Control, Closed Loop Vector Control (with encoder option)
Integrated Features DC Bus Choke (Standard), EMC Filter (Standard), Removable Graphic Keypad
Digital Inputs 4 (programmable)
Digital Outputs 2 (1 relay, 1 transistor)
Analog Inputs 2 (0/4-20mA or 0-10V, programmable)
Analog Output 1 (0/4-20mA or 0-10V, programmable)
Communication Protocols Modbus RTU (standard). Optional fieldbus cards (e.g., Profibus DP, DeviceNet, EtherNet/IP, PROFINET)
Enclosure Rating IP20 / UL Type Open (Designed for mounting inside a control panel)
Standards & Certifications CE, cULus, RoHS
Parameter Specification
Product Series Eaton PowerXL DG1
Model Number S801V50N3S
Description Variable Frequency Drive, 50A, 30kW, 400V
Rated Input Voltage 380 - 480V AC, 3-Phase, 50/60 Hz
Rated Output Current 50 A
Motor Power Rating 30 kW (40 HP) @ 400V
Overload Capacity 150% of rated current for 60 seconds
Control Methods V/F Control, Sensorless Vector Control
Integrated Features DC Bus Choke (Standard), EMC Filter (Class C2 / Category C3), Graphic Keypad
Digital Inputs 4 (programmable)
Digital Outputs 2 (programmable, relay + transistor)
Analog Inputs 2 (0/4-20mA or 0-10V, programmable)
Analog Output 1 (0/4-20mA or 0-10V, programmable)
Communication Protocols Modbus RTU (standard), Fieldbus options (e.g., Profibus DP, DeviceNet, EtherNet/IP) via plug-in modules
Enclosure Rating IP20 / UL Type Open
Standards & Certifications CE, cULus, RoHS
Parameter Specification
Product Series Eaton PowerXL DG1
Model Number S801V65N3S
Description Variable Frequency Drive, 65A, 37kW, 400V
Rated Input Voltage 380 - 480V AC, 3-Phase, 50/60 Hz
Rated Output Current 65 A
Motor Power Rating 37 kW (50 HP) @ 400V
Overload Capacity 150% of rated current for 60 seconds
Control Methods V/F Control, Sensorless Vector Control
Integrated Features DC Bus Choke (Standard), EMC Filter (Class C2 / Category C3), Graphic Keypad
Digital Inputs 4 (programmable)
Digital Outputs 2 (programmable, relay + transistor)
Analog Inputs 2 (0/4-20mA or 0-10V, programmable)
Analog Output 1 (0/4-20mA or 0-10V, programmable)
Communication Protocols Modbus RTU (standard), Fieldbus options (e.g., Profibus DP, DeviceNet, EtherNet/IP) via plug-in modules
Enclosure Rating IP20 / UL Type Open
Standards & Certifications CE, cULus, RoHS
Parameter Specification
Product Series Eaton DILM (Accessory for DILM Contactors)
Model Number DM4-340-90K
Description Auxiliary Contact Block, 4 Normally Open (4NO)
Contact Configuration 4 Normally Open (4NO)
Rated Operational Current 10A (for the auxiliary contacts)
Rated Insulation Voltage 690V
Mechanical Life High (typically millions of cycles, dependent on the main contactor)
Electrical Life High (typically hundreds of thousands of cycles at rated load)
Terminal Type Cage Clamp or Screw Terminal (specific to the -90K variant)
Mounting Side-mounting onto compatible Eaton DILM contactors.
Compatible Contactors Designed for use with specific frame sizes of DILM contactors (e.g., DILM32, DILM38, etc.). The "340" in the part number often correlates with compatibility for a specific contactor size, but must be verified with the manufacturer's datasheet.
Material Thermoplastic
Standards & Certifications CE, UL, CSA, CCC, etc., as part of the overall contactor assembly.