Parameter Specification
Product Series Eaton IZM
Model Number IZM67N3-AC40WH
Description Molded Case Circuit Breaker, 400A, 3-Pole, Fixed Mount
Frame Size IZM67
Rated Current (In) 400 A (Fixed)
Number of Poles 3
Rated Operational Voltage (Ue) 480V AC
Rated Insulation Voltage (Ui) 690V AC
Trip Unit Type AC Trip Unit (Fixed Setting)
Mounting Fixed
Operating Handle White (WH)
Standards & Certifications IEC 60947-2, UL 489, CCC, CE
Parameter Specification
Product Series Eaton ELD6 (Electronic Accessory for D6 MCB)
Model Number ELD6-6/1N/C/003
Description Electronic Residual Current Release Module, for 1P+N MCB, Curve C, 30mA Type A
Compatible With Eaton D6 series, 2-pole (1P+N), C-curve Miniature Circuit Breakers
Max. Rated Current of Assembly Up to the rating of the MCB it is attached to (e.g., 6A, 10A, 16A, 20A, etc.)
Rated Residual Operating Current (IΔn) 30 mA
Residual Current Type Type A (for alternating and pulsating direct currents)
Technology Electronic (Requires auxiliary power from the monitored circuit to operate)
Rated Voltage 230V AC
Mounting Snaps onto the side of a compatible D6 MCB on a DIN Rail.
Standards & Certifications IEC 61009-1, CE
Parameter Specification
Product Series Eaton ED6
Model Number ED6-40/1N/C/003
Description Residual Current Circuit Breaker (RCCB), 2-Pole, 40A, 30mA, Type AC
Number of Poles 2 Poles (1 Phase + Neutral)
Rated Current (In) 40 A
Rated Residual Operating Current (IΔn) 30 mA
Rated Voltage (Ue) 230V AC
Rated Short-circuit Capacity (Icn) 10 kA
Residual Current Type Type AC (for alternating sinusoidal residual currents only)
Tripping Characteristic Instantaneous
Overcurrent Protection No (Requires backup protection by an MCB or fuses)
Mechanical Life 20,000 cycles
Electrical Life 2,000 cycles
Mounting DIN Rail (35mm)
Standards & Certifications IEC 61008-1, CE
Parameter Specification
Product Series Eaton ED6
Model Number ED6-20/1N/C/003
Description Residual Current Circuit Breaker (RCCB), 2-Pole, 20A, 30mA, Type AC
Number of Poles 2 Poles (1 Phase + Neutral)
Rated Current (In) 20 A
Rated Residual Operating Current (IΔn) 30 mA
Rated Voltage (Ue) 230V AC
Rated Short-circuit Capacity (Icn) 10 kA
Residual Current Type Type AC (for alternating sinusoidal residual currents only)
Tripping Characteristic Instantaneous
Overcurrent Protection No (Requires backup protection by an MCB or fuses)
Mechanical Life 20,000 cycles
Electrical Life 2,000 cycles
Mounting DIN Rail (35mm)
Standards & Certifications IEC 61008-1, CE
Parameter Specification
Product Series Eaton ED6
Model Number ED6-20/1N/C/003
Description Residual Current Circuit Breaker (RCCB), 2-Pole, 20A, 30mA, Type AC
Number of Poles 2 Poles (1 Phase + Neutral)
Rated Current (In) 20 A
Rated Residual Operating Current (IΔn) 30 mA
Rated Voltage (Ue) 230V AC
Rated Short-circuit Capacity (Icn) 10 kA
Residual Current Type Type AC (for alternating sinusoidal residual currents only)
Tripping Characteristic Instantaneous
Overcurrent Protection No (Requires backup protection by an MCB or fuses)
Mechanical Life 20,000 cycles
Electrical Life 2,000 cycles
Mounting DIN Rail (35mm)
Standards & Certifications IEC 61008-1, CE
Parameter Specification
Product Series Eaton ED6X (Accessory for D6 MCB)
Model Number ED6X-20/1N/C/003
Description Residual Current Release Module, for 1P+N MCB, 20A, Curve C, 30mA AC
Compatible With Eaton D6 series, 2-pole (1P+N), C-curve Miniature Circuit Breakers
Max. Rated Current of Assembly Up to 20A (When combined with a compatible D6 MCB)
Rated Residual Operating Current (IΔn) 30 mA
Residual Current Type Type AC (for alternating sinusoidal residual currents only)
Rated Voltage 230V AC
Mounting Snaps onto the side of a compatible D6 MCB on a DIN Rail.
Standards & Certifications IEC 61009-1, CE
Parameter Specification
Product Series Eaton ED6
Model Number ED6-16/1N/D/003
Description Residual Current Circuit Breaker (RCCB), 2-Pole, 16A, 30mA, Type A
Number of Poles 2 Poles (1 Phase + Neutral)
Rated Current (In) 16 A
Rated Residual Operating Current (IΔn) 30 mA
Rated Voltage (Ue) 230V AC
Rated Short-circuit Capacity (Icn) 10 kA
Residual Current Type Type A (for alternating and pulsating direct currents)
Tripping Characteristic Instantaneous
Overcurrent Protection No (Requires backup protection by an MCB or fuses)
Mechanical Life 20,000 cycles
Electrical Life 2,000 cycles
Mounting DIN Rail (35mm)
Standards & Certifications IEC 61008-1, CE
Parameter Specification
Product Series Eaton ED6X (Accessory for D6 MCB)
Model Number ED6X-16/2/C/003
Description Residual Current Release Module, for 2-Pole MCB, 30mA
Compatible With Eaton D6 series, 2-pole Miniature Circuit Breakers
Rated Current of Assembly Up to 25A (When combined with a compatible D6 MCB)
Rated Residual Operating Current (IΔn) 30 mA
Residual Current Type Type AC (for alternating sinusoidal residual currents only)
Rated Voltage 230V AC
Mounting Snaps onto the side of a compatible D6 MCB on a DIN Rail.
Standards & Certifications IEC 61009-1, CE
Parameter Specification
Product Series Eaton D6
Model Number D6-16/1N/C/003-A
Description Miniature Circuit Breaker (MCB), 2-Pole, 16A, Curve C
Number of Poles 2 Poles (1 Phase + Neutral)
Rated Current (In) 16 A
Tripping Characteristic Curve C (5-10 x In)
Rated Operational Voltage (Ue) 230/400V AC
Rated Insulation Voltage (Ui) 500V AC
Rated Impulse Withstand Voltage (Uimp) 4 kV
Rated Short-circuit Breaking Capacity (Icn) 6 kA
Mechanical Life 20,000 cycles
Electrical Life 10,000 cycles
Mounting DIN Rail (35mm)
Standards & Certifications IEC 60898-1, CE
Parameter Specification
Product Series Eaton ED6
Model Number ED6-10/1N/C/003-A
Description Residual Current Circuit Breaker (RCCB), 2-Pole, 25A, 30mA
Number of Poles 2 Poles (1 Phase + Neutral)
Rated Current (In) 25 A
Rated Residual Operating Current (IΔn) 30 mA
Rated Voltage (Ue) 230V AC
Rated Short-circuit Capacity (Icn) 10 kA
Residual Current Type Type AC (for alternating currents only)
Tripping Characteristic Instantaneous
Overcurrent Protection No (Requires backup protection by MCB or fuses)
Mechanical Life 20,000 cycles
Electrical Life 2,000 cycles
Mounting DIN Rail (35mm)
Standards & Certifications IEC 61008-1, CE